The test criterion is: 115.2kbps, 80m cable. 1 router and 10 mstp master devices, max_master=127, no NPDU traffic on bus, define non used mac as fast device.
|
Router mac |
Fast device timeout config |
Other device’s mac |
Token pass rate(round/min) |
Percentage Base no fast |
|
127 |
—- |
117~126 |
2301 |
100% |
|
127 |
0ms |
117~126 |
4856 |
211% |
|
127 |
1ms |
117~126 |
4734 |
206% |
|
127 |
2ms |
117~126 |
4473 |
194% |
|
116 |
0ms |
117~126 |
4690 |
204% |
|
116 |
1ms |
117~126 |
4577 |
199% |
|
116 |
2ms |
117~126 |
4343 |
189% |
|
58 |
—- |
117~126 |
1777 |
100% |
|
58 |
0ms |
117~126 |
4563 |
257% |
|
58 |
1ms |
117~126 |
4405 |
248% |
|
58 |
2ms |
117~126 |
4071 |
229% |
|
110 |
—- |
0,11,22,33,44,55,66,77,88,99 |
1153 |
100% |
|
110 |
0ms |
0,11,22,33,44,55,66,77,88,99 |
4037 |
350% |
|
110 |
1ms |
0,11,22,33,44,55,66,77,88,99 |
3813 |
331% |
|
110 |
2ms |
0,11,22,33,44,55,66,77,88,99 |
3393 |
294% |