The test criterion is: 115.2kbps, 80m cable. 1 router and 10 mstp master devices, max_master=127, no NPDU traffic on bus, define non used mac as fast device.
| 
 Router mac  | 
 Fast device timeout config  | 
 Other device’s mac  | 
 Token pass rate(round/min)  | 
 Percentage Base no fast  | 
| 
 127  | 
 —-  | 
 117~126  | 
 2301  | 
 100%  | 
| 
 127  | 
 0ms  | 
 117~126  | 
 4856  | 
 211%  | 
| 
 127  | 
 1ms  | 
 117~126  | 
 4734  | 
 206%  | 
| 
 127  | 
 2ms  | 
 117~126  | 
 4473  | 
 194%  | 
| 
 116  | 
 0ms  | 
 117~126  | 
 4690  | 
 204%  | 
| 
 116  | 
 1ms  | 
 117~126  | 
 4577  | 
 199%  | 
| 
 116  | 
 2ms  | 
 117~126  | 
 4343  | 
 189%  | 
| 
 58  | 
 —-  | 
 117~126  | 
 1777  | 
 100%  | 
| 
 58  | 
 0ms  | 
 117~126  | 
 4563  | 
 257%  | 
| 
 58  | 
 1ms  | 
 117~126  | 
 4405  | 
 248%  | 
| 
 58  | 
 2ms  | 
 117~126  | 
 4071  | 
 229%  | 
| 
 110  | 
 —-  | 
 0,11,22,33,44,55,66,77,88,99  | 
 1153  | 
 100%  | 
| 
 110  | 
 0ms  | 
 0,11,22,33,44,55,66,77,88,99  | 
 4037  | 
 350%  | 
| 
 110  | 
 1ms  | 
 0,11,22,33,44,55,66,77,88,99  | 
 3813  | 
 331%  | 
| 
 110  | 
 2ms  | 
 0,11,22,33,44,55,66,77,88,99  | 
 3393  | 
 294%  |