Activation Of BACRouter Basic

BACRouter Basic (or BACRouter-S Basic) is the entry-level version of the BACnet router. It supports routing between BACnet/IP networks (IP–IP) or between IP and Ethernet.

By purchasing the Feature Activation, BACRouter Basic can be upgraded to the full-featured BACRouter with a single click.

The image below shows the “System Settings” page of BACRouter Basic.

To activate: Click the “To Activate” button to upgrade directly to the full feature version.

If the configuration PC does not have internet access:

Click “Manually Activate” — a QR code will be displayed.

Scan the QR code to open the activation webpage.

Obtain a 6-digit activation code from the webpage.

Enter the code and click “Submit” to complete the activation.

After activation, the “System Settings” page will show “Already activated”:

ARC156 and Multiple Frame Ratio

One of ARCNET’s greatest feature is determinacy. It has several design decisions to help it being deterministic.

  • Only 1 packet can be sent for each token pass.
  • The max payload of a packet is limited to 507 bytes.
  • Every delay is strictly limited.

So for ARC156, the time of the token passing a node is about 40.1 milliseconds in worst case that the node has a non-broadcast packet with 507 bytes payload to send and the propagation delay is extreme.

If a node has no packets to send, neglecting propagation delay, it only take 448 microseconds for the token passing. It’s very fast comparing to ms/tp.

In BACnet network, most packets have less than 50 bytes. For example, a ReadProperty request relayed from BACnet IP to ARC156 has only 25 bytes payload, a typical respond has only 32 bytes payload.

If there is a ARC156 bus with 30 nodes, one of nodes is router which relays packets from/to BACnet IP network. For each token passing round, the router sends one ReadProperty request asking for Present_Value property of Analog object in one of other nodes which replies a Complex ACK.  The time for the a passing round is about  21.4 milliseconds, so the throughout is 1/21.4 = 0.0467 transaction per milliseconds.

If we allow the router to send multiple request when it holds a token but passes token out before it has used token for 40.1 milliseconds,  the throughout will be improved while the determinacy is not degraded.

For example, if the router send 10 requests to different nodes before it passes the token out, it only takes 36.7 milliseconds. Nodes with request received will send reply when token is passing them. The total time for a token passing round is about 90.8 milliseconds.  The throughout is 10/90.8 = 0.11 transaction per milliseconds, it is about 2.36 times as standard implementation.

“Multiple Frame Ratio” parameter for BACRouter’s ARC156 port defines how long time BACRouter can hold the token to send multiple packets. For example, If “Multiple Frame Ratio” is 0.5,  then BACRouter can hold the token for 0.5 * 40.1 milliseconds = 20 milliseconds. 40.1 milliseconds here is the longest time a node can hold token we discussed at the begin.

BACRouter Changlog v6.00+

BACRouter switched to ARM soc from v6.00.  Now the firmware file format is xxxx_xxxx_6.00_arm_xxxx.tar.gz

For firmware version prior to v6.00, please visit: old firmware

Any unit with hardware >= 2.00 can not be upgraded to firmware version < 6.23

6.23 2026.03.29  Download

Introduce “Feature Activation”.

6.22 2025.11.01  Download

Bugfix for Modbus and FreeClient: In very noisy environment, RS485 communication may stall.

6.21 2025.10.30

Modbus mapping output objects add support to “write only” via setting output feature.  If a output object is write-only, its reliability property will be NO_OUTPUT when startup until a write command is received, then it will keep writing last command for every “offline update interval”.

6.20 2025.10.28  Download

WebUI Bug from v6.10: In device runtime info dialog of “Modubs Master Module” and “Free Client Module”, when button to modify present value is clicked, if the device has disabled point defined, wrong point may be selected.

6.19 2025.10.15  Download

UART decoder was improved. It has better noise immunity with start bit adjusting.

6.18  2025.10.04

Modbus bug on MultipleStateInput object introdued by v4.34: when a MSI object is mapped to holding register, its present value will not be updated.

Modbus WebUI bug on MultipleState object’s state string editing starting from v6.00 is fixed.

6.17  2025.09.27

Improvement over v6.16: Global broadcast now has a independent block rule.

6.16  2025.09.13

New feature: Relay block function allows user defined expression to control which packet is allowed to be relayed. Please access it on the “Network Settings” page.

6.15  2025.09.02  Download

A bug was introduced by v6.13. “Read coil from discrete” works reversed in the daemon, that is said, the daemon read coil from discrete when the flags is unset.  The WebUI still takes right value when performing “Test read”.

When MSTP runtime info page on WebUI calcuates “Token pass rate”, there may be a “Divide by 0” except which will restart the daemon. It is usually triggered when token just start to pass.

6.14  2025.08.22

WebUI bug on Modbus TCP: Test will fail when slave address is out of range of 1~247 (The valid range of slave address for Modbus TCP is 0~255).

6.13  2025.06.02  Download

Modbus module now support device that its holding register or coil is write only, but the value of holding register and coil could be read from input register or discrete input at the same address offset. Please check “Read redirect” in “Modbus parameter”.

ARC156 revert change in last version: Give up recovery from noise after passing token.

6.12  2025.04.29  Download

ARC156:  If next station had been verified, when passing token failed, retry it once.

ARC156: If a frame lasts less than 5 bits,  regards it as noise.

6.11  2025.04.02  Download

ARCnet standard and Datasheet of COM20019i state that the accuracy of clock should be 0.01% or better, so our previous implementation utilize a conservative clock error correction logic to tolerate clock error to 0.05%. After testing ZN551 and AAR module, we found they actually tolerate clock error up to 4.5% when decoding packets(The reconfiguration process still require clock error less than 0.2%), they are supposed to synchronize receiver clock to pulse preceding every byte. In this version, we implement a aggressive logic to achieve similar or better performance.

6.10  2025.03.28

ARC156:  The “Nodes on the bus” runtime info may detect non-existed node when two segments of bus with active nodes join together.  The workaround is double detecting to avoid false signal.

ARC156:  If BACRouter is the sole node on the bus, it will keep sending ITT(Invite To Transmit) to look for other nodes, none data packet can be sent. any NPDU sent to this port will be timed-out on the queue, then it will be annoying in the log. In this version, if BACRouter find itself is sole node on the bus, it will delete packet on the queue at a reasonable rate, and record it on the packet capture buffer to pretend sending the packet out. So when investigating packet captured, BACRouter are sending packets but get no response, this behavior is consistent to other data-link type.

Modbus RTU:  Some devices do not respect T15 between bytes, we remove the verify to improve compatibility.

Application Settings:  “Client Mode” is removed to comply to BTL requirement.

Modbus/FreeClient: When debugging the mapping or script, Writing from BACnet side usually need to be perform, user has to launch a BACnet client for example Yabe. There is often a BACnet server already running on the computer, so user has to start a VM to run Yabe. It wastes a lot time, so we integrate write function on the runtime info page.

6.09  2025.02.26  Download

MSTP bug to manipulate hardware will cause certain NPDU body discarded.

6.08  2025.01.23  Download

WebUI bug on Modbus Master Module:

When “Write Test” analog object mapping to single register, the byte order should respect to “Byte order for single register”, not “Byte order for big integer”.

When “Write Test” multi-state object mapping to 2 registers, the byte order should respect to “Byte order for big integer”, not “Byte order for single register”

The real value of binary object of free client device in “Runtime Info” page should respect to polarity setting.

6.07  2025.01.10  Download

Because BACRouter highly rely on high resolution timer, If there is electromagnetic disturbance, the crystal on the board may be disturbed, so timer will drift, lead to program malfunction.  We add correct function in this version.

6.06  2025.01.07  Download

Bugfix for free client module’s binary output object. It was introduced by v6.01 Polarity feature.

Modbus master module: when writing to read only data address, some devices respond timeout instead of report a exception, which will cause BACRouter keeps trying and fails with offline. For this version, BACRouter will only try 3 times then gives up.

6.05  2025.01.04

Refactor low level arc156 and ms/tp drivers to simplify code.

ARC156 driver add logic to drop packet send to node responding excess NAK to Free Buffer Enquiry

WebUI: Remind user when IP or netmask has been changed but DHCP server keeps enabled,

6.04  2024.12.26  Download

Fix bug on ms/tp:  Sending packet to ms/tp port with NPDU length near 1497 bytes may trigger the bug.

6.03  2024.12.25

ARC156 is usable now.

6.01  2024.12.06

Fixed bug on bus name collision detection for Modbus/Free Client module.

Free Client:  Bianry objects add “Polority” attribute. Multistate objects add state quantity limitation of 256.

Offline configuration and import/export

From firmware v4.x,Offline configuration had been introduced. Now user could configure a BACRouter without device on hand, then export configuration to a file. When commissioning on the field, user just need to import previously exported file, “Save&Reboot” to take effect the configuration.

From v4.04,The object definitions for Modbus gateway could be import/export as CSV format. User could effectively setup object to Modbus address mapping In batches with Excel/WPS/Libreoffice, then import it to WebUI for detailed modify.

Offline configure on our website  (IE will not work now)

Download and extract it to disk, open index.html by your web browser (Because IE/Edge doesn’t support Local Storage for file:// URL, the user library for binary text and most used engineering unit will not be kept after leaving the web page)

There are 3 types of configuration file:

BACRouter Configuration File

This type of configuration file keeps all settings in BACRouter. If the firmware version of exporting one is same to importing one, WebUI should not complain of the configuration file.

Modbus Master Configuration File

This type of configuration file keeps setting under the scope of Modbus master.  When importing it, collision detecting logic based on current mapping mode will check every enabled slave in this master, if collision is found, the slave will be disabled.

If the master is RTU/ASCII type, it may also be disabled if there are contention for RS485 port.

With these problem, WebUI will prompt user to re-check configuration.

Modbus Slave Configuration File

This type of configuration file keeps setting under the scope of Modbus slave.  When importing it, if collision detecting logic based on current mapping mode found problem, the slave will be disabled.

It is allowed to import TCP salve configuration file in RTU/ASCII master, and vice versa, but the slave may be disabled if Modbus parameter setting do not work.

With these problem, WebUI will prompt user to re-check configuration.

Modbus Gateway in BACRouter

Update on 2023-03-07  for version 4.26

From firmware version 4.x,  BACRouter has builtin Modbus gateway functionality. This article will try to explain the underlying mechanism.

Modbus Read

BACRouter will periodically read point’s value and cache it.  “Update interval” defines how often BACRouter update the value.

To improve performance, BACRouter will read as more as possible data in one transcation. In Modbus standard, at most 2000 bits (coil or discrete) or 125 registers (input or holding register) could be read in one request, but specific Modbus slave device may only support a lower value.  In BACRouter’s WebUI, there is a Modbus parameter edit dialog in “Slave Settings”, “Multiply read bits” and “Multiply read registers” parameters define the ability of the slave device.

BACRouter will not segment reading of single point even the “Multiply read registers” is less than registers used by the point.

Usually the data we care for has discontinuous Modbus address, for example, We only care for coils on address 1 and 2000, though we could read coil data from address 1 to 2000 in one request and skip returned data from address 2 to 1999,  sending two requests independently for coil on address 1 and coil on address 2000 maybe more efficient. “Bits skipped” and “Registers skipped” parameter define how many unused data units between 2 cared data units are allowed to be skipped. As previous example, if “Bits skipped” is set to 1998, the BACRouter will try to read coil 1 and 2000 in single request. If “Bits skipped” is set to 1997, then BACRouter will read Coil 1 first, then Coil  2000, because bits skipped is 1998 and is greater than the setting of 1997.

On the WebUI page for slave, the “Read Group” button will show how the BACRouter will group the reading and test it. User should pay special attention on server exception of “Illegal data address”.

Modbus Write

BACRouter will not combine multiple writing demand into one writing request. It always queue write request immediately after receiving command.

For writing single data unit, there are two Modbus function codes available. For example, function code 5 is writing single coil,  function code 15 is writing multiple coils but the quantity of coil to write could be assigned to 1. Some devices only support one of them.  “Coil write singly” parameter will specify which function code is used.

In the same way, “Register write singly” is applied to register writing. If any BACnet output object maps to multiple holding registers, it implies the slave device support function code 16 for write multiple registers, “Register write singly” will be automatically disabled, function code 16 will be used for writing any register.

Offline

If any read/write request failed, BACRouter will retry it, when the continuous fail count reachs 3, BACRouter will regard the slave device as offline. In offline state, BACRouter will retry the request every “Offline update interval”.

The BACnet side reaction for offline event will be described later.

Modbus Serial Bus

BACRouter supports serial slave devices with different baudrate, parity, RTU/ASCII mode on same RS485 bus. Before sending request, BACRouter will change it serial port parameter based on slave device’s settings.

It should be safe to have 2 devices with same slave address but different baudrate or RTU/ASCII  mode, but preventing collision based on different parity might not be enough, because some devices do not examine parity error.

Single Device Mapping Mode

If VBUS network port is not enabled, BACRouter will work in single device mapping mode, every Modbus slave device will be mapped into exclusive object instance space of 1000 in the only BACnet device defined in “Application Settings”.

The actual BACnet object name will be organized as “master_name|slave_name|object_name”,  The “|” is name delimiter which could be selected from dozen of characters by user.

As recommended by standard, BACRouter will create one StructuredView object for each slave device.

When the slave device turn to offline in this mode, all points’ reliability will be set to “COMMUNICATION_FAILURE”, if slave device is back to online, upon updating of point value, the point’s reliability will be set back to “NO_FAULT_DETECTED”.

Virtual Device Mapping Mode

If VBUS network port is enabled. Each slave device will be mapped to a virtual BACnet device on VBUS network. The MAC address will start from 1.

In this mode, each slave shall has a unique “Device instance”. The BACnet device name of the slave will be “master_name|slave_name”, The delimiter “|” is select-able.

When the slave device turn to offline in this mode, as recommended by standard, the virtual BACnet device will stop sending/receiving any packet to simulate offline state. if slave device is back to online, after updating all point’s value, the virtual BACnet device will quite offline state.

Slave Device’s Status

For every slave device, BACRouter will create 3 objects in gateway device, one object is Binary_Input with name of “online”, which represents online/offline status of slave device. another object is Analog_Input with name of “update_delay”, which is recently average update time delayed over “”Update interval”, the last one is Analog_Input with name of “fail_rate”,  which count a relative long time fail rate on Modbus side.

Those objects’ name have prefix of “master_name|slave_name|comm|”, where “|” is select-able delimiter.

Object Instance Assignment

Object Instance is defined for every object. When the editor dialog for a object is submitted and the object is enabled, the object instance claimed by the object will be assigned, if that assigning fail, a automatically selected instance will be used.

Value Object

AV/BV/MV is behaving same as AI/BI/MI, except that when AV/BV/MV is mapped to writable Modbus address (0X or 4X), the present value of the object is writable, the writing will be forwarded to Modbus side (See below 2 exceptions).

Exception 1:  If AV is mapped to holding register, its data type is customized, but the binding script doesn’t support output, that AV will be read only.

Exception 2:  If AV is mapped to multiple holding registers, but the”Register write singly” option is enabled, that implies output will not be supported, so the AV will be read only.

Output Object

The value of output object is still being polled from Modbus side and set to object’s Relinguish_Default property. If the value read back does not match last value written, BACRouter will set the reliability of that object to “UNRELIABLE_OTHER”,  and BACRouter will queue another write after a certain time. When “Tolerate unmatch” option is enabled, If the value read back does not match last value written, the reliability of that object keeps unchanged, and BACRouter will re-write the value on “Offline update interval”. (Update for v4.34)

Because of above verifying mechanism,  the BACRouter will prevent defining two output objects with overlaping Modbus writable address.

NaN For Float And Double

NaN is a special value defined by IEEE-754, BACRouter does not accept NaN (Infinite is still valid for BACRouter).

When a point is defined as Float and Double, but NaN is read from slave, BACRouter will set the reliability to “UNRELIABLE_OTHER”.

Unsupported value for script

When a analog object is customized, but the Modbus to BACnet conversion reports unsupported value from the script,  that object’s reliability will be set to “UNRELIABLE_OTHER”.

For a Analog Output object, when the BACnet to Modbus conversion reports unsupported value from the script, the object’s reliability will be set to  “PROCESS_ERROR”

For a Analog Value object, when the BACnet to Modbus conversion reports unsupported value from the script, that output attempt will be dropped, the object’s reliability will be unchanged.

Interoperability between extended MS/TP frame capable devices and legacy devices

Original BACnet MS/TP data link specification only supports NPDU length up to 501 bytes, which is much shorter than 1497 bytes of Ethernet and IP data link. It limits transmission performance, increases complexity on application layer, especial when two IP/Ethernet networks are conjoined by a MS/TP network.

Extended frame was designed to solve this problem. The detail could be found here. Briefly, this addendum added two new frame types as:

  • 32: BACnet Extended Data Expecting Reply
  • 33: BACnet Extended Data Not Expecting Reply

Frame type 32 is extended from frame type 5 (BACnet Data Expecting Reply),  the special of it is that it is encoded by COBS and the NPDU length it carried is in range of 502 to 1497 bytes.

In the same way, frame type 33 is extended from frame type 6 (BACnet Data Not Expecting Reply)

Extended frame support was added into BACnet standard since revision 16. There are still lot of devices installed or on the market that do not support it. The interoperability between extended frame capable devices and legacy device is discussed below.

  • Non-router legacy device and extended frame capable device: Because all messages sent to legacy device are application layer message, the “Max APDU Length Accepted” from Device object property or confirmed service request primitive should be respected, the NPDU length will not exceed 501 bytes. So there are no problem with this configuration.
  • Legacy router and extended frame capable device: NPDU that should be relayed to other network through legacy router with length over 501 bytes will be discarded, no reject-message-to network with reason “Message Too Long” will be responded. Even more, the “Max APDU Length Accepted” of legacy router may be determined by other port that has a NPDU length larger than 501 bytes (It is allowed by standard), so NPDU for local application layer sent to legacy router will still possibly be carried by extended frame and discarded. So this configuration may cause problem in field.

BACRouter supports extended frame from very early version. From firmware version 3.18, we introduced “Extended frame” option on BACRouter’s MS/TP configuration, if there are legacy router that does not support extended frame on the bus, this option should be disabled to avoid Interoperability issues.

It’s worth noting that even “Extended frame” option is disabled, unlike legacy router, BACRouter will still be interoperable with extended frame capable devices.

(Screenshot has been updated on Aug 5, 2021. Because extended frame is mandatory from standard revision 16, from firmware 4.13, we move this option to extended configure mode.)