UART Decode Algorithm And Noise Immunity

Background

Most serial protocols in BAS domain are based on UART (Universal Asynchronous Receiver/Transmitter), e.g. Modbus, MS/TP.

The data stream consists of bytes. Each byte is a UART frame with 4 elements: start bit, 5 to 9 data bits, parity bit if has,  1 or 2 stop bits. Wikipedia for reference.  

The basic algorithm inside UART decoder includes bit sampling and start bit detection, they all affect performance of noise immunity.

Bit Sampling

There are three most common sampling algorithms: single sampling, majority vote, debounce.

Single Sampling

It is the most easy method that samples at the middle of bit. It is very sensitive to noise.

Majority Vote

A optimized sampling method is to take several samples near the middle of bit, then determine the value by majority vote.

In practice, a common design is using 16 times over sampling, 3 samples will be taken on 8th, 9th, 10th sample clock. The value is determined by at least 2 samples with identical value.  But if the width of noise signal is wider than 1/16 bit, 2 false values may be sampled.

Debounce

It’s another over sampling method. If the debounce time is 2 samples, only 2 consecutive samples have same value, the value will be confirmed, otherwise old value will be kept, so single sample noise will be filtered. But if the width of noise signal is wider than 1 sample, 2 consecutive false values may be sampled.

Start Bit Detection

Detection of start bit is critical for decoder to synchronize with sender. That is where “Asynchronous” coming from. There are 3 common detection algorithms on market: falling edge, falling edge with start bit validation, complicated others.

Detect Start Bit By Falling Edge

This method recognizes falling edge as start bit, no more validation will be taken. It is unguarded to noise. For a RS485 bus in idle state, electromagnetic interference is easy to cause noise signal leading to false start bit.

Detect Start Bit By Falling Edge With Start Bit Validation

This method is mainstream on the market. It does not only detect falling edge, it also samples the start bit (uses algorithm mentioned above), if value 0 is sampled, then the start bit is validated. if not, it regards the falling edge as noise then searches another falling edge.

By validation the start bit, it has a much better noise immunity, but for RS485 bus in idle state, this method still has some drawbacks:

  • If the noise width is near half of bit, it may be regarded as start of bit.
  • If there are 2 noise signals, the second one occurs near 1/2 bit after first one. then both falling edge and start bit validation are satisfied.
  • If the noise signal occurs less than 1/2 bit ahead of falling edge of real start bit. The middle start bit sample will read real start bit and pass validation. So the detected start bit will be ahead of real start bit to 1/2 bit most, that may cause error on later data bit sampling.

Detect Start Bit With Other Complicated Algorithms

MCUs from STMicroelectronics and Freescale (now NXP) have a complicate Algorithms to detect start bit, all three criteria below should be satisfied:

  • A: Falling edge should has 3 leading 1.
  • B: At least 2 samples of 0 should be found on 3th, 5th, 7th of clock.
  • C: At least 2 samples of 0 should be found on 8th, 9th, 10th of clock.

This algorithms works very well in noisy environment, but complicated algorithms usually lead to bug, For example:

When logic level switches from 1 to 0, a noise wider than 1/16 bits occurs at specific position. The falling edge at 1th clock will not meet rule C, so the decoder will skip it and search other falling edge, because there is no other falling edge meeting rule A, no start bit will be detected. (It had been confirmed on STM32F072RB)

Algorithm Of BACRouter From v6.00+

We implement a 32 times oversampling filter, for each slide window with 32 samples, if the number of 1 is greater than 21, value 1 is outputted, if the number of 1 is less than 11, value 0 is outputted, otherwise the value same as previous slide window is outputted.

Then the bit sampling and detection of start bit will be very simple.  Every bit is sampled at the middle of bit. The start bit detection need to search for the falling edge only.2025.10.15: To achieve better performance when start bit is interfered by noise, or there is baud rate difference between sender and receiver, We implement start bit adjusting by every edge.

This algorithm has excellent noise immunity:

  • Noise width less than 2/3 bit will not lead to false start bit on a idle RS485 bus.
  • Noise width less than 1/3 bit will not affect bit sampling
  • Noise ahead of real start bit will only advance decoded start bit.

The only situation that it performs worse than traditional decoder is that the noise width or signal distortion is more than 1/3 bit and signal at the middle of bit is still valid.

The filter also works for ARC156.

CCN Gateway Changelog

Download&Extract the zip file, there are 2 firmware files inside it, one is for BACnet version, another is for Modbus version.

For CCN Gateway with firmware version prior to v3.00, please go to the bottom of page.

3.09  2025.11.01  Download

Bugfix: In very noisy environment, RS485 communication may stall.

CCN: Allow string points in  CONFIG or SERVICE tables, but writing to them is not supported yet.

3.08  2025.10.04

CCN communication performance is improved.

BACnet Mapping of String point:  the unit should be NO_UNITS, not SQUARE_METERS.

3.07  2025.06.06

Carrier has a localized air cooled heat pump serial in Chinese market.  30RQVHS is one of the model. We found its A1/B1 terminals talks CCN and Modbus RTU slave at the same time. Its CCN timing is a bit different to other chillers. The central control panel writes to its SERVICE table to control it.

This version modifies CCN timing to be compatible with it, and supports CONFIG and SERVICE tables.

3.06  2025.04.10  Download

Fix bug that “IP Router” setting will be lost after reboot.

3.05  2025.02.26

Fix bug that may crash the daemon when there is collision on the CCN bus.

Updates BACnet ms/tp driver from BACRouter 6.09

2.26  Download

Most Versatile Modbus Gateway

BACRouter has a powerful Modbus master module, but there are still some scenarios that it can not handle well, for examples:

  1. Point’s value is read from register 3×00001, but has to write to register 4×00001(From v6.15 and v5.14, new “Read coil from discrete” and “Read holding from input” features resolved it).
  2. Value 1 read from Modbus mapping to BACnet 1.0, but writing BACnet value 1.0 to Modbus has to write 10. (Lua script for Modbus master module can do asymmetrical conversion for customized Analog object)
  3. Analog/Multistate object mapping to several Modbus coils or discrete inputs.
  4. Write only Modbus data address, read from it will report timeout or exception.(It is supported from v6.21 and v5.19 by “write only” output feature of output object)

Fortunately,  we have free client module which can implement a most versatile Modbus gateway by Lua script.  We host the modbus.lua scripts on github.com

For modbus.lua, all devices under a bus share same baudrate/parity/timeout property. For Modbus master module, each device under a bus has independent timing property.

User should try Modbus master module at first, because of the test feature of Modbus master module, user can rapidly verify the mapping setting.

After all normal points have been setup, there may leave some weird points,  you should test read for those points.

Then the “Read Group” will verify the grouping.

Then you should export the device’s setting.

There is a fcmbconv.py python program on github repository, install python and run it, it will promote you to choose modbus.lua, then the device config file you had exported, then it will create a free client bus config file for the device.

Then import the created config into BACRouter under “Free Client Module”.

At last you have to modify the special settings for those weird points.

Example:

We assume there is a device, has several normal points, and

1. Analog output objects “lamp1” and “lamp2” get on/off status from bit 0 and bit 1 of Register 4×00032,  value 1 on the corresponding bit means on, value 0 means off.  To turn on/off of lamps, register 4×00031 should be written, but the value 1 on the corresponding bit means turning off, value 0 means turning on.

2. 8 bits from 1×00008 map to analog input object “temperature3”.

3. Write-only register 4×00100(Read will report timeout), low byte maps analog output object “load1”, high byte maps to analog output object “load2”.

Setup a Modbus device: ExampleModbusDevice,  verify the grouping by “Read Group”
Using fcmbconv.py to convert it to:  FCModbus

Import it into free client module:

Modify setting for weird points.

For lamp1:

For temperature3:

For load1 and load2:

Finally, verify its behavior by Yabe. If the script fails, please check the log.

The final config file for the free client bus is:  FCModbusFinal

Modbus Devices Config & Lua Scripts & Conversion

Modbus Device Config

Siemens_RDF302.jsonSiemens RD302 Thermostat
Schneider_TC500.jsonSchneider TC500 Thermostat
JCI_T8600.jsonJCI T8600 Thermostat
JCI_T7000.jsonJCI T7000 Series Thermostat
ABB_ACS510.jsonABB ACS510 VFD

Lua Script

bcd.luaEach byte is 0-9, for example: 0x05090702 = 5972
Endian is defined by “big integer”
compat_bcd.luaEach half byte is 0-9, for example: 0x78695231 = 78695231
Endian is defined by “big integer”
m10k.luaEach register is -9999~9999, for example: 0x1f740a69 = 0x1f74*10000 + 0x0a69 = 80522665
Endian is defined by “big integer”
low10th.luaOnly 1 register, low byte is one tenth, the range is 0.0 to 255.9 for example: 0x0503 = 5.3
Endian is defined by “single integer”.
This is found in York TMS2100 FCU thermostat.

Conversion

Convert BASgatewayLX CSV Configuration

Convert BASgatewayLX CSV Configuration To BACRouter JSON

BASgatewayLX (Hereinafter referred to as LX) supports CSV configuration file. There are decent documents about the format and dozens of configuration samples for vary devices on their website. The convert tool we provided could convert the CSV file to JSON file which could be imported in BACRounter’s WebUI to create a Modbus slave station.

Convert on our website

Download and extract it to disk, open index.html by your web browser

Matters need attention:

Though LX claims the object name should be unique, but the accessory “Profile Checker” does not check duplicated object name. We found a lots duplicated object names in the samples. So we decided to disable object with duplicated name in converting.

Some CSV files have characters out of UTF8 code page, we guess they are ISO-8859-1 encoding. So if we fail to decode CSV by UTF8, we fall back to ISO-8859-1.

LX supports maximum 64 bytes of object name and description (With ISO-8859-1 encoding?). BACRouter supports 64 bytes too, but with UTF8 encoding. There has possibility that 64 bytes in ISO-8859-1 is larger than 64 bytes when encoding as UTF8. We will tail-cut too long name and description and promote to user.

BACRouter doesn’t allow 2 output objects mapped to overlapped Modbus address, but LX seems to allow it. We will disable the conflicted object in converting.

LX defines register order for every 32 bits data, but BACRouter has to set unitary byte order for all objects. If the consistent byte order definitions are found when converting, the previous definition will be accepted, the conflict will be promoted to user.

BACRouter has object instance range of 0~999 for every slave, but LX seems no limitation. If instance larger than 999 is found, the object will be auto assigned a new instance.

Offline configuration and import/export

From firmware v4.x,Offline configuration had been introduced. Now user could configure a BACRouter without device on hand, then export configuration to a file. When commissioning on the field, user just need to import previously exported file, “Save&Reboot” to take effect the configuration.

From v4.04,The object definitions for Modbus gateway could be import/export as CSV format. User could effectively setup object to Modbus address mapping In batches with Excel/WPS/Libreoffice, then import it to WebUI for detailed modify.

Offline configure on our website  (IE will not work now)

Download and extract it to disk, open index.html by your web browser (Because IE/Edge doesn’t support Local Storage for file:// URL, the user library for binary text and most used engineering unit will not be kept after leaving the web page)

There are 3 types of configuration file:

BACRouter Configuration File

This type of configuration file keeps all settings in BACRouter. If the firmware version of exporting one is same to importing one, WebUI should not complain of the configuration file.

Modbus Master Configuration File

This type of configuration file keeps setting under the scope of Modbus master.  When importing it, collision detecting logic based on current mapping mode will check every enabled slave in this master, if collision is found, the slave will be disabled.

If the master is RTU/ASCII type, it may also be disabled if there are contention for RS485 port.

With these problem, WebUI will prompt user to re-check configuration.

Modbus Slave Configuration File

This type of configuration file keeps setting under the scope of Modbus slave.  When importing it, if collision detecting logic based on current mapping mode found problem, the slave will be disabled.

It is allowed to import TCP salve configuration file in RTU/ASCII master, and vice versa, but the slave may be disabled if Modbus parameter setting do not work.

With these problem, WebUI will prompt user to re-check configuration.

Modbus Gateway in BACRouter

Update on 2023-03-07  for version 4.26

From firmware version 4.x,  BACRouter has builtin Modbus gateway functionality. This article will try to explain the underlying mechanism.

Modbus Read

BACRouter will periodically read point’s value and cache it.  “Update interval” defines how often BACRouter update the value.

To improve performance, BACRouter will read as more as possible data in one transcation. In Modbus standard, at most 2000 bits (coil or discrete) or 125 registers (input or holding register) could be read in one request, but specific Modbus slave device may only support a lower value.  In BACRouter’s WebUI, there is a Modbus parameter edit dialog in “Slave Settings”, “Multiply read bits” and “Multiply read registers” parameters define the ability of the slave device.

BACRouter will not segment reading of single point even the “Multiply read registers” is less than registers used by the point.

Usually the data we care for has discontinuous Modbus address, for example, We only care for coils on address 1 and 2000, though we could read coil data from address 1 to 2000 in one request and skip returned data from address 2 to 1999,  sending two requests independently for coil on address 1 and coil on address 2000 maybe more efficient. “Bits skipped” and “Registers skipped” parameter define how many unused data units between 2 cared data units are allowed to be skipped. As previous example, if “Bits skipped” is set to 1998, the BACRouter will try to read coil 1 and 2000 in single request. If “Bits skipped” is set to 1997, then BACRouter will read Coil 1 first, then Coil  2000, because bits skipped is 1998 and is greater than the setting of 1997.

On the WebUI page for slave, the “Read Group” button will show how the BACRouter will group the reading and test it. User should pay special attention on server exception of “Illegal data address”.

Modbus Write

BACRouter will not combine multiple writing demand into one writing request. It always queue write request immediately after receiving command.

For writing single data unit, there are two Modbus function codes available. For example, function code 5 is writing single coil,  function code 15 is writing multiple coils but the quantity of coil to write could be assigned to 1. Some devices only support one of them.  “Coil write singly” parameter will specify which function code is used.

In the same way, “Register write singly” is applied to register writing. If any BACnet output object maps to multiple holding registers, it implies the slave device support function code 16 for write multiple registers, “Register write singly” will be automatically disabled, function code 16 will be used for writing any register.

Offline

If any read/write request failed, BACRouter will retry it, when the continuous fail count reachs 3, BACRouter will regard the slave device as offline. In offline state, BACRouter will retry the request every “Offline update interval”.

The BACnet side reaction for offline event will be described later.

Modbus Serial Bus

BACRouter supports serial slave devices with different baudrate, parity, RTU/ASCII mode on same RS485 bus. Before sending request, BACRouter will change it serial port parameter based on slave device’s settings.

It should be safe to have 2 devices with same slave address but different baudrate or RTU/ASCII  mode, but preventing collision based on different parity might not be enough, because some devices do not examine parity error.

Single Device Mapping Mode

If VBUS network port is not enabled, BACRouter will work in single device mapping mode, every Modbus slave device will be mapped into exclusive object instance space of 1000 in the only BACnet device defined in “Application Settings”.

The actual BACnet object name will be organized as “master_name|slave_name|object_name”,  The “|” is name delimiter which could be selected from dozen of characters by user.

As recommended by standard, BACRouter will create one StructuredView object for each slave device.

When the slave device turn to offline in this mode, all points’ reliability will be set to “COMMUNICATION_FAILURE”, if slave device is back to online, upon updating of point value, the point’s reliability will be set back to “NO_FAULT_DETECTED”.

Virtual Device Mapping Mode

If VBUS network port is enabled. Each slave device will be mapped to a virtual BACnet device on VBUS network. The MAC address will start from 1.

In this mode, each slave shall has a unique “Device instance”. The BACnet device name of the slave will be “master_name|slave_name”, The delimiter “|” is select-able.

When the slave device turn to offline in this mode, as recommended by standard, the virtual BACnet device will stop sending/receiving any packet to simulate offline state. if slave device is back to online, after updating all point’s value, the virtual BACnet device will quite offline state.

Slave Device’s Status

For every slave device, BACRouter will create 3 objects in gateway device, one object is Binary_Input with name of “online”, which represents online/offline status of slave device. another object is Analog_Input with name of “update_delay”, which is recently average update time delayed over “”Update interval”, the last one is Analog_Input with name of “fail_rate”,  which count a relative long time fail rate on Modbus side.

Those objects’ name have prefix of “master_name|slave_name|comm|”, where “|” is select-able delimiter.

Object Instance Assignment

Object Instance is defined for every object. When the editor dialog for a object is submitted and the object is enabled, the object instance claimed by the object will be assigned, if that assigning fail, a automatically selected instance will be used.

Value Object

AV/BV/MV is behaving same as AI/BI/MI, except that when AV/BV/MV is mapped to writable Modbus address (0X or 4X), the present value of the object is writable, the writing will be forwarded to Modbus side (See below 2 exceptions).

Exception 1:  If AV is mapped to holding register, its data type is customized, but the binding script doesn’t support output, that AV will be read only.

Exception 2:  If AV is mapped to multiple holding registers, but the”Register write singly” option is enabled, that implies output will not be supported, so the AV will be read only.

Output Object

The value of output object is still being polled from Modbus side and set to object’s Relinguish_Default property. If the value read back does not match last value written, BACRouter will set the reliability of that object to “UNRELIABLE_OTHER”,  and BACRouter will queue another write after a certain time. When “Tolerate unmatch” option is enabled, If the value read back does not match last value written, the reliability of that object keeps unchanged, and BACRouter will re-write the value on “Offline update interval”. (Update for v4.34)

Because of above verifying mechanism,  the BACRouter will prevent defining two output objects with overlaping Modbus writable address.

NaN For Float And Double

NaN is a special value defined by IEEE-754, BACRouter does not accept NaN (Infinite is still valid for BACRouter).

When a point is defined as Float and Double, but NaN is read from slave, BACRouter will set the reliability to “UNRELIABLE_OTHER”.

Unsupported value for script

When a analog object is customized, but the Modbus to BACnet conversion reports unsupported value from the script,  that object’s reliability will be set to “UNRELIABLE_OTHER”.

For a Analog Output object, when the BACnet to Modbus conversion reports unsupported value from the script, the object’s reliability will be set to  “PROCESS_ERROR”

For a Analog Value object, when the BACnet to Modbus conversion reports unsupported value from the script, that output attempt will be dropped, the object’s reliability will be unchanged.